Temperature transducers for Pt100 and Ni100 sensors
TYPE | LXR-800 | LXR-801 | LXR-811 |
Photo | |||
Schematic | |||
INPUT | |||
RTD sensor | Pt100, Ni100 | ||
Line resistance | ≤100 Ω / cable | ||
Line compensation | automatic | ||
Sensor current | ~0,5 mA | ||
OUTPUT | |||
2-wire current loop | 4…20 mA | ||
Current output | 0…20 mA | ||
Voltage output | 0…10 V | ||
POWER SUPPLY | |||
From current loop | |||
Supply voltage range | 24 VDC (20…30 VDC) |
8…30 VDC | 9…30 VDC |
Power supply current | ≤30 mA | ||
OTHER | |||
Basic accuracy | ≤0,1% | ||
Sensor break signalization (max / min) | / | / | / |
Sensor linearization | Pt100 | ||
Galvanic isolation | input / output | ||
Galvanic isolation (test) | 1500 VAC | ||
Working temperature | 0…70°C | ||
Protection (housing / teminals) | IP20 / IP20 | ||
Mounting | DIN rail | ||
CONFIG | |||
Config | according to the order | ||
OPTIONS | |||
One / two-channel | / | / | / |
Other input / output ranges (on request) | / | / — | / — |
DOCUMENTS | |||
Data sheet | Download | Download | Download |